Switch Settings - YASKAWA MP2100 Series User Manual

Machine controller design and maintenance
Table of Contents

Advertisement

4 Specifications

4.3.3 Switch Settings

4.3.3 Switch Settings
The following table shows the switch settings of the MP2100.
Mode Switch 1
(1) Mode Switch 1 (S1)
No.
Name
1
INIT
2
STOP
(2) Mode Switch 2 (S2)
No.
Name
1
TEST
2
MON
3
CNFG
4
SUP
5
SLOT0
6
SLOT1
* Set the CP number allocated to the communication process logic port. When using two or more
MP2100s, set different CP number.
(3) Reset Switch
This switch resets the MP2100.
This switch can be used to turn ON and OFF the MP2100 power without turning the host computer ON and OFF.
4-8
Mode Switch 2
ON
1
2
Status
Function
ON
Memory Clear
OFF
Normal operation
ON
User program stopped
OFF
User program running
Status
Function
ON
System use
OFF
Normal operation
ON
System use
OFF
Normal operation
ON
Configuration mode
OFF
Normal operation
ON
System use
OFF
Normal operation
SLOT
- SLOT0
 
1
- ON
CP4
ON
- OFF
CP3
ON
- ON
CP2
OFF
- OFF
CP1
OFF
Reset Switch
Factory
Setting
OFF
Set to ON to clear memory. If this switch is set
to OFF, the program stored in flash memory will
be executed.
OFF
Stops the user program execution. Enabled only
when the power is turned ON.
Factory
Setting
OFF
Always leave set to OFF.
OFF
Always leave set to OFF.
OFF
Set to ON to execute self-configuration for
connect devices.
OFF
Always leave set to OFF.
OFF
Use to set CP number.
OFF
Details
Details

Advertisement

Table of Contents
loading

This manual is also suitable for:

Japmc-mc2100Mp2100m seriesJapmc-mc2140

Table of Contents