F34895
VSM DRIVE-CLiQ (CU): Alternating cyclic data transfer error
Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, TM150, TM31, VECTOR_G
Reaction:
Vector: NONE (OFF1, OFF2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Voltage Sensing Module involved (VSM) to the Control
Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
F34896
VSM DRIVE-CLiQ (CU): Inconsistent component properties
Message value:
Component number: %1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, TM150, TM31, VECTOR_G
Reaction:
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (Voltage Sensing Module), specified by the fault value, have changed
in an incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ
cable or DRIVE-CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be
used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the
original cables should be used (ensure compliance with the maximum cable length).
F34899 (N, A)
VSM: Unknown fault
Message value:
New message: %1
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Reaction:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault occurred on the Voltage Sensing Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Voltage Sensing Module by an older firmware version (r0158).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE