Siemens SINAMICS G150 Manual page 1727

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Sensor Module by an older firmware version (r0148).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon F:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F34207 (N, A)
VSM: Temperature fault threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Reaction:
Vector: NONE
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3668).
Note:
This fault can only be initiated if the temperature evaluation was activated (p3665 = 2 for a KTY sensor or p3665 = 1
for a PTC sensor).
Fault value (r0949, interpret decimal):
yyxxxx dec:
yy: Component number of the component which detected the fault.
Remedy:
- check the fan.
- reduce the power.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A34211 (F, N)
VSM: Temperature alarm threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3667).
Alarm value (r2124, interpret decimal):
The hundred-thousands and ten-thousands position specifies the component number of the VSM which detected the
fault.
Remedy:
- check the fan.
- reduce the power.
Reaction upon F:
Vector: NONE
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1727

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130