Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- upgrade TM54F firmware to more recent version.
- contact the Hotline.
- replace the TM54F.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F35053
TM54F: Temperature fault threshold exceeded
Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this fault.
As fault response fail-safe input terminal signals are transferred to the motion monitoring functions.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).
A35054
TM54F: Temperature alarm threshold exceeded
Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this alarm.
Remedy:
- allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).
A35075 (F)
TM54F: Error during internal communication
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An internal communications error has occurred in the Terminal Module 54F (TM54F).
This message is also output in the following cases:
- The TM54F exists and no safety function of the TM54F has yet been parameterized.
- Parameter p10000 (TM54F master) is not set the same as p10000 (TM54F slave).
- Parameter p10010 (TM54F master) is not set the same as p10010 (TM54F slave).
Alarm value (r2124, interpret decimal):
Only for internal Siemens diagnostics.
Remedy:
If TM54F exists and no safety function has yet been parameterized:
- Not necessary. The alarm disappears automatically after a safety function of the TM54F has been parameterized.
For p10010/p10000 from the TM54F master not equal to the TM54F slave:
- start the copy function for the node identifier on the TM54F (p9700 = 1D hex).
- acknowledge the hardware CRC on the TM54F (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (power off/on) for all components.
For internal communication errors:
- check the electrical cabinet design and cable routing for EMC compliance
- upgrade the software on the TM54F.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1749