4 Faults and alarms
4.2 List of faults and alarms
A34903 (F, N)
VSM: I2C bus error occurred
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred when accessing the module-internal I2C bus.
Remedy:
Replace the Terminal Module.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A34903 (F, N)
VSM: I2C bus error occurred
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
B_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred when accessing the module-internal I2C bus.
Remedy:
Replace the Voltage Sensing Module (VSM).
Reaction upon F:
NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A34904 (F, N)
VSM: EEPROM
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred accessing the non-volatile memory on the Terminal Module.
Remedy:
Replace the Voltage Sensing Module (VSM).
Reaction upon F:
Vector: NONE
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A34905 (F, N)
VSM: Parameter access
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Control Unit attempted to write an illegal parameter value to the Voltage Sensing Module (VSM).
Remedy:
- check whether the firmware version of the VSM (r0158) matches the firmware version of Control Unit (r0018).
- if required, replace the Voltage Sensing Module.
Note:
The firmware versions that match each other are in the readme.txt file on the memory card.
Reaction upon F:
Vector: NONE
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)