4 Faults and alarms
4.2 List of faults and alarms
bb = 1A hex: p10046
bb = 1B hex: p10041
bb = 1C hex: p10046
bb = 1D ... 1F hex: p10017, p10002, p10000
bb = 20 ... 2A hex: p10040, p10046, p10047
bb = 2B hex: error in the data for test stop initialization
bb = 2C hex: error in the data for initializing the input/output calculation
bb = 2D ... 45 hex: error in the data for the output calculation p10042 ... p10045
bb = 46 ... 63 hex: error in the data for the calculation of drive group 1
bb = 64 ... 81 hex: error in the data for the calculation of drive group 2
bb = 82 ... 9F hex: error in the data for the calculation of drive group 3
bb = A0 ... BD hex: error in the data for the calculation of the drive group 4
bb = BE hex: debounce time of the fail-safe inputs (F-DI) p10017
bb = BF hex: debounce time of the single-channel inputs (DI) p10017
bb = C0 hex: debounce time of the Diag inputs p10017
bb = C1 hex: error in the internal data for p10030 SDI positive
bb = C2 hex: error in the internal data for p10031 SDI negative
bb = C3 ... CA hex: error in the data to calculate the drive groups p10030 ... p10031
bb = CB hex: p10032
bb = CC hex: p10033
bb = CD hex: p10009
bb = CE ... CF error in the data for drive group 1 SLP parameter p10032 ... p10033
bb = D0 ... D1 error in the data for drive group 2 SLP parameter p10032 ... p10033
bb = D2 ... D3 error in the data for drive group 3 SLP parameter p10032 ... p10033
bb = D4 ... D5 error in the data for drive group 4 SLP parameter p10032 ... p10033
bb = D6 error in the data for initializing the retract function
bb = D7 error in the data for the retract function SLP
bb = D8 error in parameter p10000[1..5]
bb = D9..E3 error in the internal data of the axis communication
bb = E4..F2 error in the internal data of the discrepancy check
cc: indicates the index of the data to be cross-compared that resulted in the error.
Remedy:
Carry out the following steps on the TM54F:
- check the specified parameters for incorrect parameterization.
- activate the safety commissioning mode (p0010 = 95).
- start the copy function for SI parameters (p9700 = 57 hex).
- acknowledge complete data change (p9701 = AC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1).
- carry out safe acknowledgment (p10006).
For an internal software error (aaaa > 0):
- For TM54F, upgrade the firmware to a later version.
- contact the Hotline.
- replace the TM54F.
F35052 (A)
TM54F: Internal hardware error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software/hardware error has been detected on the Terminal Module 54F (TM54F).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
1748
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents