4 Faults and alarms
4.2 List of faults and alarms
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A33700
Encoder 3: Effectivity test does not supply the expected value
Message value:
Fault cause: %1 bin
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DRIVE-CLiQ encoder fault word supplies fault bits that have been set.
Fault value (r0949, interpret binary):
Bit x = 1: Effectivity test x unsuccessful.
Remedy:
Replace encoder.
N33800 (F)
Encoder 3: Group signal
Message value:
-
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
VECTOR_G
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
NONE
Cause:
The motor encoder has detected at least one fault.
Remedy:
Evaluate the other messages that are presently available.
Reaction upon F:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
F33801 (N, A)
Encoder 3 DRIVE-CLiQ: Sign-of-life missing
Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
VECTOR_G
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the encoder involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F33802 (N, A)
Encoder 3: Time slice overflow
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
VECTOR_G
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A time slice overflow has occurred in encoder 3.