Avaya G700 Maintenance Manual page 234

Gateway/ server or an
Hide thumbs Also See for G700:
Table of Contents

Advertisement

6 Avaya MultiVantage Software-Controlled Maintenance:
Table 71. TEST #144 Slip Alarm Inquiry Test Continued
Error
Test
Code
Result
1 to
FAIL
88
1 to
FAIL
88
(cont'd.)
(cont.)
PASS
234
Description/ Recommendation
The test failed because the DS1-MM interface Media Module and the
remote DS1 endpoint are not synchronized to the same clock rate.
The DS1-MM interface Media Module detected a slip alarm. The error
code equals the number of slips detected by the DS1-MM interface
Media Module since the last slip alarm inquiry test.
If the DS1-MM connects to a T1 network facility or to another switch,
do the following:
Retry the command at 1-minute intervals for a maximum of 5
times.
For a DS1 interface Media Module, enter the list measurement
ds1-log GGGVS command to read the error seconds
measurement.
Verify that both endpoints of the DS1 link are administered using
the same signaling mode, framing mode, and line coding.
Contact T1 Network Service or the technician at the remote
switch to diagnose the remote DS1 endpoint.
Check the physical connectivity of the DS1-MM interface Media
Modules and the cable.
Replace the local DS1-MM interface Media Module, and repeat
the test.
If the DS1-MM connects to a line-side terminating device (for
example, a PRI terminal adapter), do the following:
Retry the command at 1-minute intervals for a maximum of 5
times.
Enter the list measurement ds1-log GGGVS command to read
the error seconds measurement.
Verify that the switch DS1 and the line-side terminating device
are administered using the same signaling mode, framing mode,
and line coding.
Investigate the maintenance status of the line-side terminating
device. Refer to the 'Line-Side Terminating Device Operating
Manual' for information.
Contact the vendor of the line-side terminating device to
diagnose the equipment.
Check the physical connection of the DS1-MM interface Media
Module to the terminating device, and check the premise
distribution system (or the intra-premise wiring) for physical
connection failures.
Replace the local DS1-MM interface Media Module and repeat
the test.
No Slip alarm is detected on the DS1-MM Interface Media Module.
MG-DS1 (DS1 Interface Media Module)
Maintenance for S8300/S8700 and G700
555-234-101 — Issue 2 — October 2002
2 of 3