Technical Data - ABB F-ATI Test Quick Start Manual

Rccb with automatic test
Hide thumbs Also See for F-ATI Test:
Table of Contents

Advertisement

TECHNICAL DATA /

TÉCNICAS /
SPÉCIFICATIONS TECHNIQUES
Reference Standards
Electrical features
Test features
Mechanical features
Installation
Auxiliary contact
Dimensions
SPECIFICHE TECNICHE
Distribution system
Rated voltage U
Rated frequency
Rated current I
Rated sensitivity I
Type
Poles
Insulation voltage U
Minimum test voltage U
Rated conditional short-circuit I
Rated residual current for test
Dielectric test voltage at ind. freq.
for 1 min
Rated impulse withstand voltage
(1,2/50) U
Power consumption 2P
Power consumption 4P
Power consumption during
operation
Cycle time
Protection degree
Contact position indicator CPI
Mechanical life
Tightening torque
Ambient temperature
Storage temperature
Type
Operating features
Terminals cross section
Tightening torque
DIN modules
Weight
/ LEISTUNGSMERKMALE / ESPECIFICACIONES
e
n
δn
i
tmin
nc
imp
F-ATI Test
3
ABB
EN61008-1 , VDE V 0664-120
(annex M)
TN, TT, IT
230-400 V a.c. -15% ÷ 10%
50 Hz
25, 40, 63 A
30, 300 mA
A AP-R
2P, 4P
500 V d.c.
195 V a.c.
10 kA (SCPD - gL fuse 63 A for In
25, 40 A; gL fuse 80 A for In 63 A)
49mA (Idn 30mA),460mA
(Idn 300mA)
2,5 kV
4 kV
2,2 (25A) - 5,4 (40A) - 6,2 (63A)
23,5 (25A) - 6 (40A) - 12 (63A)
41 VA
< 7 s
IP20 (terminals), IP40 (housing)
yes
4000
2 Nm
-25...+60 °C
-40...+70 °C
NO-NC-NC+pulse (100 ms)
5 ÷ 230 V a.c./d.c. I
max
2,5 mm
2
0,4 Nm
5, 7
550, 900 gr
100 mA

Advertisement