Table 6:
Analog input settings, phase currents
Parameter
Values (Range)
Primary current
1)
Secondary current
Amplitude Corr A
Amplitude Corr B
Amplitude Corr C
Nominal current
2)
Rated secondary Val
Reverse polarity
Angle Corr A
Angle Corr B
Angle Corr C
1) For CT
2) For sensor
Table 7:
Analog input settings, residual current
Parameter
Values (Range)
Primary current
Secondary current
Amplitude Corr
Reverse polarity
Angle correction
620 series
Technical Manual
Basic functions

General parameters

Unit
1.0...6000.0
A
2=1A
3=5A
0.9000...1.1000
0.9000...1.1000
0.9000...1.1000
39...4000
A
1.000...150.000
mV/Hz
0=False
1=True
-20.0000...20.0000
deg
-20.0000...20.0000
deg
-20.0000...20.0000
deg
Unit
1.0...6000.0
A
1=0.2A
2=1A
3=5A
0.9000...1.1000
0=False
1=True
-20.0000...20.0000
deg
Step
Default
0.1
100.0
2=1A
0.0001
1.0000
0.0001
1.0000
0.0001
1.0000
1
1300
0.001
3.000
0=False
0.0001
0.0000
0.0001
0.0000
0.0001
0.0000
Step
Default
0.1
100.0
2=1A
0.0001
1.0000
0=False
0.0001
0.0000
Section 3
Basic functions
Description
Rated primary current
Rated secondary current
Phase A amplitude correction factor
Phase B amplitude correction factor
Phase C amplitude correction factor
Network Nominal Current (In)
Rated Secondary Value (RSV) ratio
Reverse the polarity of the phase CTs
Phase A angle correction factor
Phase B angle correction factor
Phase C angle correction factor
Description
Primary current
Secondary current
Amplitude correction
Reverse the polarity of the residual CT
Angle correction factor