External Selection Of Auto-Reclose Mode; Reclosing Reclaim Timer; Pulsing Of The Cb Closing Command And Counter - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
MODEINT (integer)
A start of a new reclosing cycle is blocked during the set "reclaim time" after the selected
number of reclosing shots have been made.
12.2.2.14

External selection of auto-reclose mode

The auto-reclose mode can be selected by use of the available logic function blocks. Below is
an example where the choice of mode is done from a hardware function key in front of the IED
with only 3 phase or 1/3 phase mode, but alternatively there can for example, be a physical
selector switch on the front of the panel which is connected to a binary to integer function
block (BTIGAPC).
The connection example for selection of the auto-reclose mode is shown in figure 112.
IEC07000119 V3 EN-US
Figure 112: Selection of the auto-reclose mode from a hardware functional key in front of
12.2.2.15

Reclosing reclaim timer

The reclaim timer
until the reclosing function resets. Should a new trip occur during this time, it is treated as a
continuation of the first fault. The reclaim timer is started when the CB closing command is
given.
12.2.2.16

Pulsing of the CB closing command and Counter

The CB closing command, CLOSECB is given as a pulse with a duration set by parameter
tPulse . For circuit-breakers without an anti-pumping function, close pulse cutting can be used.
It is selected by parameter
command pulse is then cut (interrupted). The minimum closing pulse length is always 50 ms.
At the issue of the Reclosing command, the appropriate Reclosing operation counter is
incremented. There is a counter for each type of Reclosing and one for the total number of
Reclosing commands.
Application manual
ARMode
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
the IED
tReclaim defines the time it takes from issue of the reclosing command,
CutPulse=On . In case of a new trip pulse (start), the closing
Type of fault
1st shot
1ph
1ph
2ph
2ph
3ph
.....
1ph
1ph
2ph
2ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
3ph
IEC14000040-1-en.vsd
Section 12
Control
2nd-5th shot
3ph
.....
.....
3ph
3ph
.....
3ph
.....
.....
M12391-241 v4
M12391-202 v3
M12391-205 v3
223