Measurement Modes; Timer Characteristics - ABB RER620 Technical Manual

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
4.1.1.5
4.1.1.6
RER620
Technical Manual

Measurement modes

The function operates on four alternative measurement modes: "RMS", "DFT",
"Peak-to-Peak" and "P-to-P + backup". The measurement mode is selected with the
setting Measurement mode.
Table 102:
Measurement modes supported by 51P/50P stages
Measurement mode
RMS
DFT
Peak-to-Peak
P-to-P + backup
For a detailed description of the measurement modes, see the General
function block features section in this manual.

Timer characteristics

51P/50P supports both DT and IDMT characteristics. The user can select the timer
characteristics with the Operating curve type and Type of reset curve settings. When the
DT characteristic is selected, it is only affected by the Trip delay time and Reset delay time
settings.
The relay provides 16 IDMT characteristics curves, of which seven comply with the IEEE
C37.112 and six with the IEC 60255-3 standard. Two curves follow the special
characteristics of ABB praxis and are referred to as RI and RD. In addition to this, a user
programmable curve can be used if none of the standard curves are applicable. The user
can choose the DT characteristic by selecting the Operating curve type values "ANSI Def.
Time" or "IEC Def. Time". The functionality is identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages:
Supported measurement modes
51P
50P-1
x
x
x
x
x
x
Section 4
Protection functions
50P-2
x
87