Factory settings restoration

In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to the
original factory state. All default settings and configuration files stored in the factory
are restored. For further information on restoring factory settings, see the operation
manual.

Load profile record LDPRLRC

Function block

GUID-FE70FC2E-8582-4450-97F1-B9D699809951 V1 EN
Figure 104:
Function block

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand interval).
Up to 12 load quantities can be selected for recording and storing in a nonvolatile
memory. The value range for the recorded load quantities is about eight times the
nominal value, and values larger than that saturate. The recording time depends on a
settable demand interval parameter and the amount of quantities selected. The record
output is in the COMTRADE format.

Quantities

Selectable quantities are product-dependent.
Table 206:
Quantity Description
Disabled
Quantity not selected
IL1
Phase 1 current
IL2
Phase 2 current
IL3
Phase 3 current
Io
Neutral/earth/residual current
IL1B
Phase 1 current, B side
IL2B
Phase 2 current, B side
IL3B
Phase 3 current, B side
IoB
Neutral/earth/residual current, B side
Table continues on next page
1MRS757644 F
620 series
Technical Manual