3.3 Load Connections

Refer to paragraph 3.4 for systems with outlets. Connect the Load line (black) connection to
the output of the selected circuit breaker. Connect the Neutral (white) and Ground (green)
connections from the load to the terminal blocks identified as Neutral and Ground inside the
AC Distribution Shelf. Tighten these connections until completely secure. See Figure 3-4.
Circuit Breaker Rating
2 – 70 Amps per position
Note: All load wiring exiting this shelf must be in conduit per the National Electrical Standards.
Page 12
© Copyright 2021 ABB. All rights reserved.
Terminal Capacity
4 - 14 AWG
Ground Connections
Neutral Connections
Line Connections
Figure 3-5: Ground, Load, Neutral Connections
Loads are routed under the Neutral
connection and out the rear of the AC
Figure 3-6: Load Connections cable routing
Terminal Type
Recommended Wire Size
Compression
Dependant on load