Section 3
Basic functions
3.15.6
3.15.6.1
3.15.6.2
3.15.6.3
3.15.7
3.15.7.1
136
GOOSERCV_CMV function block
Function block
GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 51:
Function block
Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs
to the application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined
in the GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application.
Default value (0) is used if VALID output indicates invalid status.
Signals
Table 76:
GOOSERCV_CMV Output signals
Name
Type
MAG
FLOAT32
ANG
FLOAT32
VALID
BOOLEAN
GOOSERCV_ENUM function block
Function block
GUID-E1AE8AD3-ED99-448A-8C11-558BCA68CDC4 V1 EN
Figure 52:
Function block
Description
Output signal (amplitude)
Output signal (angle)
Output signal
1MRS757644 F
620 series
Technical Manual