1MRS757644 F
3.15.5
3.15.5.1
3.15.5.2
3.15.5.3
620 series
Technical Manual
GOOSERCV_INTL function block
Function block
GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 50:
Function block
Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input
to the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
Signals
Table 75:
GOOSERCV_INTL Output signals
Name
Type
POS_OP
BOOLEAN
POS_CL
BOOLEAN
POS_OK
BOOLEAN
VALID
BOOLEAN
Basic functions
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal
Section 3
135