Section 3
Basic functions
3.15
3.15.1
3.15.1.1
3.15.1.2
132
•
Monitoring/I/O status/Analog inputs
•
Monitoring/IED status/SMV traffic
•
Monitoring/IED status/SMV accuracy
GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or
PCM600.
GOOSERCV_BIN function block
Function block
GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 46:
Function block
Functionality
The GOOSERCV_BIN function is used to connect the GOOSE binary inputs to the
application.
1MRS757644 F
620 series
Technical Manual