04 - 17

AUI Input Gain

Settings
04 - 18

No AUI Negative bias command

Settings
Pr.04-00 ~ 04-03, Pr.04-11 ~ 04-18 are used when the source of frequency command is
the analog signal. Refer to the following examples.
Example 1:
Max.
Output
Freq.
60Hz
30Hz
0Hz
4mA
Example 2:
In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point
of the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any
further increase of the potentiometer will not increase output frequency. (If you want to use the
range of 60Hz, please refer to the example 3.) The value of external input voltage/current
0-8.33V (4-13.33mA) corresponds to the setting frequency 0-60Hz.
Pr.01-00
60Hz
10Hz
Bias
Adjustment
0Hz 0V
4mA
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
01 to 200%
00
No ACI Negative bias command
01
Negative bias, REV motion enabled
02
Negative bias, REV motion disabled
Pr.01-00
Pr.01-00=60Hz--Max. output Freq.
Pr.04-11=0%--bias adjustment
Pr.04-12 =0-- bias polarity
Pr.04-13=100% -- pot. freq. gain
Pr.04-14=0 -- REV disable in negative bias
0V
5V
10V
12mA
20mA
Max. Output Freq.
Pr.01-00=60Hz--Max. output Freq.
Pr.04-11=16.7%-- bias adjustment
Pr.04-12=0 -- bias polarity
Pr.04-13=100% -- pot. freq. gain
Pr.04-14=0 -- REV motion disable in negative bias
10V
5V
20mA
12mA
Factory Settings
Factory Settings
5-23
VFD-B Series
Factory Setting: 100
Unit: 1%
Factory Setting: 00
5