8-2 EMC-D42A
-- Extension card for 4-point digital input/ 2-point digital input
MI10–MI13
I/O Extension
Card
MO10–MO11

8-3 EMC-D611A

- Extension card for 6-point digital input (110V
-
I/O Extension
Card
MI10–MI15
Terminals
Common for Multi-function input terminals
COM
Select SINK (NPN) / SOURCE (PNP) in J1 jumper / external
power supply
Refer to Pr.02-26–02-29 to program the multi-function inputs
MI10–MI13.
Internal power is applied from terminal E24: +24 V
mA, 5W
External power +24 V
V
, 30W
DC
ON: the activation current is 6.5 mA
OFF: leakage current tolerance is 10 μA
Multi-function output terminals (photocoupler)
The AC motor drive releases various monitor signals, such as
drive in operation, frequency attained and overload indication, via
transistor (open collector).
Common for multi-function output terminals MO10, MO11
MXM
(photocoupler)
Max 48 V
Terminals
AC
AC power Common for multi-function input terminal (Neutral)
Refer to Pr.02-26–Pr. 02-31 for multi-function input selection
Input voltage: 100–130 V
Input frequency: 47–63 Hz
Input impedance: 27 KΩ
Terminal response time:
ON: 10 ms
OFF: 20 ms
Descriptions
: max. voltage 30 V
DC
50 mA
DC
AC
Descriptions
AC
8-15
Chapter 8 Option CardsC2000 Plus
± 5% 200
DC
, min. voltage 19
DC
MO10
MO11
MXM
input voltage)