Communication Parameters (09) Group - Delta CP2000 Series Quick Start Manual

Fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

Chapter 3 Set Up the VFD Parameters | CP2000
Parameter
Display Text
07-12 Speed
Restart Method
search on startup
07-33 Auto
Reset
restart internal of
RestartCNT
fault (Internal
time counter for
faults)

Communication Parameters (09) group

These parameters are only necessary if you are planning to communicate to the built-in BACnet
interface in the drive.
Parameter
Display Text
09-31 Internal
COM1 Protocol
communication
protocol
Description of Parameter
This determines how the
drive starts the motor. This is
a useful setting if the drive
occasionally starts when the
motor is already spinning.
Parameter options:
0 – Disable. Wait for the
motor to stop spinning
before next start.
1 – Speed search, starting
from maximum frequency
(normally 60Hz).
2 – Speed search, starting
from motor start frequency
(normally 0.5Hz).
3 – Speed search, starting
from minimum frequency.
When a restart occurs after
a fault, the drive starts this
internal time clock and
counts the number of faults
that occur within this time
period. If the number of
faults do not exceed the
number recorded in the 07-
11 parameter, the time clock
and fault are reset back to
zero.
When the number of faults
exceed the 07-11 parameter
value, the drive faults and
stops, requiring user
intervention.
Description of Parameter
Set up the protocol
communication used.
Parameter options:
0 – Modbus
1 – BACnet MS/TP
12
Default
Preferred
Value
Value
0
3
60 secs
60 secs
Default
Preferred
Value
Value
0
1

Advertisement

Table of Contents
loading