Allocations for the CPU Unit
PORT_A
PORT_A
PORT_B
PORT_C
For details of bank and file memory of EM area, refer to "SYSMAC CS Series
CS1G/H-CPU __ -EV1, CS1G/H-CPU __ H Programmable Controllers Opera-
tion Manual (Cat. No. W339-E1-@@)".
• First address (word m+5)
When CIO (0001), WR (0002), DM (0003), or EM area (0004) is specified
for the operation data area in the area type specification (word m+4 bit08
to 14), the first address is to be specified.
Set the first address in hexadecimal (Hex). The setting range varies de-
pending on the setting of the No. of transferred words (word m+4 bit00 to
07).
When setting the No. of transferred words to its maximum "A0 Hex (160)",
the setting ranges are as follows:
CIO area: 0000 to 175F Hex (0 to 5983)
WR area: 0000 to 015F Hex (0 to 351)
DM area: 0000 to 7F5F Hex (0 to 32607)
EM area: 0000 to 7F5F Hex (0 to 32607)
When "Does not use the general I/O area (00)" is specified in the area type
specification (word m+4 bit 08 to 14), this setting is not necessary.
Setting example
Ex1:
General I/O A
m+4
(PORT_A)
m+5
0Ahex (10) words of the custom I/O area starting from word 4E20Hex (20000)
in EM area of PLC are transferred to input variables of MC Unit (IW0B00~).
On PLC
EM 20000 to 20009
Ex2:
m+4
General I/O A
(PORT_A)
m+5
m+6
General I/O B
(PORT_B)
m+7
m+8
General I/O C
(PORT_C)
m+9
m+10
General I/O D
(PORT_D)
m+11
m+12
General I/O E
(PORT_E)
m+13
m+14
General I/O F
(PORT_F)
m+15
m+16
General I/O G
(PORT_G)
+17m
m+18
General I/O H
(PORT_H)
m+19
The custom I/O area is allocated to the memory area of PLC as shown below:
On PLC
CIO 0000 to 0009
CIO 5000 to 5099
WR 200 to 204
840A
4E20
Direction
→
IW 0B00 to 0B09
010A
0000
8164
1388
8205
00C8
84A0
2710
0000
0000
810A
000A
03A0
7D00
0328
7DA0
Direction
←
OW 0B00 to 0B09
→
IW 0BA0 to 0C03
→
IW 0C40 to 0C43
Section 7-3
On MC Unit
On MC Unit
369