Current Based Inverse Definite Minimum Time Characteristics; Idmt Curves For Overcurrent Protection - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 9
General function block features
9.2
9.2.1
442
A070422 V1 EN
Figure 217:
Operating effect of the BLOCK input when the selected blocking mode
is "Freeze timer"
If the BLOCK input is activated when the operate timer is running, as described in
Figure
217, the timer is frozen during the time BLOCK remains active. If the timer
input is not active longer than specified by the Reset delay time setting, the operate
timer is reset in the same way as described in
input .
The selected blocking mode is "Freeze timer".
Current based inverse definite minimum time
characteristics

IDMT curves for overcurrent protection

In inverse-time modes, the operation time depends on the momentary value of the
current: the higher the current, the faster the operation time. The operation time
calculation or integration starts immediately when the current exceeds the set Start
value and the START output is activated.
Figure
215, regardless of the BLOCK
1MRS757454 D
611 series
Technical Manual