Operation Principle - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
6.1.3
Phasor measurement unit RES670 2.2 IEC
Application manual
Figure
33
shows both instances of ANALOGREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are three separate ANALOGREPORT blocks capable of reporting up to 24
Analog signals (8 Analog signals in each ANALOGREPORT block). These can
include for example transfer of active and reactive power or reporting the
milliampere input signals to the PDC clients as defined in IEEE C37.118 data
frame format.
IEC140000120 V2 EN-US
Figure 33:
Multiple instances of ANALOGREPORT blocks
Figure
34
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate BINARYREPORT blocks capable of reporting up to 24 Binary
signals (8 Binary signals in each BINARYREPORT block). These binary signals
can be for example dis-connector or breaker position indications or internal/
external protection alarm signals.
IEC140000121 V2 EN-US
Figure 34:
Multiple instances of BINARYREPORT blocks

Operation principle

The Phasor Measurement Unit (PMU) features three main functional principles:
Wide area measurement system
IEC140000120-2-en.vsd
IEC140000121-2-en.vsd
GUID-EB2B9096-2F9D-4264-B2D2-8D9DC65697E8 v3
Section 6
89