Z2: Bypass Control Input/Output - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Z1-98: Minimum Drive SW Ver
No.
Name
(Hex.)
Z1-98
Minimum Drive SW Ver
(8627)
Expert
Z1-99: Maximum Drive SW Ver
No.
Name
(Hex.)
Z1-99
Maximum Drive SW Ver
(8628)
Expert

Z2: Bypass Control Input/Output

Z2-01 to Z2-08 Digital Input 1 to 8 Function Selection
The drive has 8 digital input terminals. Refer to
No.
Z2-01
Digital Input 1 Function Select (TB2-1)
Z2-02
Digital Input 2 Function Select (TB2-2)
Z2-03
Digital Input 3 Function Select (TB2-3)
Z2-04
Digital Input 4 Function Select (TB2-4)
Z2-05
Digital Input 5 Function Select (TB2-5)
Z2-06
Digital Input 6 Function Select (TB2-6)
Z2-07
Digital Input 7 Function Select (TB2-7)
Z2-08
Digital Input 8 Function Select (TB2-8)
Setting Value
0
Not Used
1
Drive S1 Passthrough
2
Drive S2 Passthrough
3
Drive S3 Passthrough
4
Drive S4 Passthrough
5
Drive S5 Passthrough
6
Drive S6 Passthrough
7
Drive S7 Passthrough
21
Run (AUTO)
22
Run Enable - Safety (NC)
23
Run Interlock (BAS)
24
Remote Transfer to Bypass
25
Emergency Override Bypass
26
Emergency Override Drive (FWD)
27
Motor OR Select
28
Motor AND Select
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
"WARNING: If these parameters are changed, undesired operation of the bypass system could occur.
These parameters should only be changed under guidance of Yaskawa technical support (1-800-
YASKAWA)."
"WARNING: If these parameters are changed, undesired operation of the bypass system could occur.
These parameters should only be changed under guidance of Yaskawa technical support (1-800-
YASKAWA)."
Table 5.70
Table 5.70 Digital Input Default Settings and Functions
Name
Table 5.71 Digital Input Setting Values
Function
Reference
444
444
444
444
444
444
444
445
445
445
445
445
445
445
445
445
Description
Description
for default settings and functions.
Default
21
Run (AUTO)
22
Run Enable - Safety (NC)
23
Run Interlock (BAS)
24
Remote Transfer to Bypass
25
Emergency Override Bypass
0
Not Used
0
Not Used
0 or 29
Not Used or External Overload Motor 1 (NC)
Setting Value
29
External Overload Motor 1 (NC)
30
External Overload Motor 2 (NC)
31
HAND Select
32
AUTO Select
33
Drive/Bypass Select
34
Fault Reset
35
External Fault (EF0)
36
External Fault (EFB)
37
Run Reverse (AUTO)
38
Fire Stat Switch (NC)
39
Freeze Stat Switch (NC)
40
Smoke Alarm (NC)
41
OverPressure Switch (NC)
42
Low Suction Switch (NC)
43
Vibration Switch (NC)
44
Emergency Override Drive (REV)
5.14 Z: Bypass Parameters
Default
(Range)
01011
00000 - 65535
Default
(Range)
01011
00000 - 65535
Function
Function
Reference
445
446
446
446
446
446
446
446
446
446
446
446
447
447
447
447
5