Code
Name
Note:
• The drive detects this error if it does not correctly receive control data for the CE detection time set to H5-09 [CE Detection Time].
• Do a Fault Reset to clear the fault.
• If the drive detects this error, the drive will operate the motor as specified by the stopping method set in H5-04 [Communication Error Stop Method].
Code
Name
CoF
Current Offset Fault
Note:
• The drive detects this error if the current offset value is more than the permitted setting range while the drive automatically adjusts the current offset.
• Do a Fault Reset to clear the fault.
Code
Name
CPF00
Control Circuit Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF01
Control Circuit Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF02
A/D Conversion Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF03
Control Board Connection Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Causes
Electrical interference caused a communication data
error.
Causes
The drive starts operation while the induced voltage
stays in the motor (during coasting to a stop or after
fast deceleration).
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Possible Solutions
• Examine the control circuit lines, main circuit lines, and ground
wiring, and decrease the effects of electrical interference.
• Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
• Use only the recommended cables or other shielded line. Ground
the shield on the controller side or the drive input power side.
• Separate the communication wiring from drive power lines, and
install a noise filter to the input side of the power supply for
communication.
• Decrease the effects of electrical interference from the controller.
Possible Solutions
• Make a sequence that does not restart operation when induced
voltage stays in the motor.
• Set b3-01 = 1 [Speed Search at Start Selection = Enabled].
• Use Speed Search from Fmax or Fref [H1-xx = 61, 62] to do a
speed search through one of the external terminals.
Replace the drive.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.