Advertisement

5.7 H: Terminal Functions
OFF : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03.
L4-03: Speed Agree Detection Level(+/-)
Figure 5.55 Example of Frequency Detection 4 (Value of L4-03 is Positive)
17: Torque Detection 1 (N.C.)
Setting Value
Function
17
Torque Detection 1 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque <
L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to
L6: Torque Detection on page 336
18: Torque Detection 2 (N.O.)
Setting Value
Function
18
Torque Detection 2 (N.O.)
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-
05 for longer than the time set in L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 336
19: Torque Detection 2 (N.C.)
Setting Value
Function
19
Torque Detection 2 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque <
L6-05 for longer than the time set in L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 336
1A: During Reverse
Setting Value
Function
1A
During Reverse
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
286
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
The terminal activates when the drive detects overtorque or undertorque.
for more information.
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
The terminal activates when the motor operates in the reverse direction.
L4-04: Speed Agree Detection Width(+/-)
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference