9.17 Z: Bypass Parameters
No.
Name
(Hex.)
Z2-08
Digital Input 8 Function
(TB2-8)
(856A)
Z2-09
Digital Input 1 Invert
Select
(856B)
Z2-10
Digital Input 2 Invert
Select
(856C)
Z2-11
Digital Input 3 Invert
Select
(856D)
Z2-12
Digital Input 4 Invert
Select
(856E)
Z2-13
Digital Input 5 Invert
Select
(856F)
Z2-14
Digital Input 6 Invert
Select
(8570)
Z2-15
Digital Input 7 Invert
Select
(8571)
Z2-16
Digital Input 8 Invert
Select
(8572)
Z2-23
Digital Output 7 (TB1
1~3)
(8579)
Z2-24
Digital Output 8 (TB1
4~6)
(857A)
Z2-25
Digital Output 9 (TB1
7~9)
(857B)
Z2-26
Digital Output 10 (TB1
10~12)
(857C)
Z2-30
Analog Input Signal
Level Select
(8580)
Z2-32
Analog Input Gain
Setting
(8582)
Z2-33
Analog Input Bias Setting Sets the bias of the analog signal input to MFAI terminal A1.
(8583)
Z2-xx: Digital Input Setting Values
Setting Value
Function
0
Not Used
1
Drive S1 Passthrough
2
Drive S2 Passthrough
3
Drive S3 Passthrough
4
Drive S4 Passthrough
5
Drive S5 Passthrough
6
Drive S6 Passthrough
7
Drive S7 Passthrough
668
Sets the function for bypass digital input 8.
Inverts the output of the function selected in Digital Input 1.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 2.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 3.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 4.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 5.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 6.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 7.
0 : Normal (Non-inverted)
1 : Inverted
Inverts the output of the function selected in Digital Input 8.
0 : Normal (Non-inverted)
1 : Inverted
Sets the function for bypass digital output 7.
Sets the function for bypass digital output 8.
Sets the function for bypass digital output 9.
Sets the function for bypass digital output 10.
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
Sets the gain of the analog signal input to MFAI terminal A1.
Use this setting for unused terminals or to use terminals in through mode.
Drive Multi-function input S1.
Drive Multi-function input S2.
Drive Multi-function input S3.
Drive Multi-function input S4.
Drive Multi-function input S5.
Drive Multi-function input S6.
Drive Multi-function input S7.
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
0
442
(0 - 47)
0
443
(0, 1)
0
443
(0, 1)
0
443
(0, 1)
0
443
(0, 1)
0
443
(0, 1)
0
443
(0, 1)
0
444
(0, 1)
0
444
(0, 1)
7
448
(0 - 99)
10
448
(0 - 99)
12
448
(0 - 99)
15
448
(0 - 99)
0
452
(0 - 3)
100.0%
452
(-999.9 - +999.9%)
0.0%
452
(-999.9 - +999.9%)
Ref.
444
444
444
444
444
444
444
445