YASKAWA HV600 Technical Reference page 606

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.6 C: Tuning
C4: Torque Compensation
No.
Name
(Hex.)
C4-01
Torque Compensation
Gain
(0215)
RUN
C4-02
Torque Compensation
Delay Time
(0216)
RUN
C6: Carrier Frequency
No.
Name
(Hex.)
C6-02
Carrier Frequency
Selection
(0224)
C6-03
Carrier Frequency Upper
Limit
(0225)
C6-04
Carrier Frequency Lower
Limit
(0226)
C6-05
Carrier Freq Proportional
Gain
(0227)
606
Sets the gain for the torque compensation function. Use this parameter value for motor 1
when you operate multiple motors.
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
Sets the carrier frequency for the transistors in the drive.
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
7 : Swing PWM1 (Audible Sound 1)
8 : Swing PWM2 (Audible Sound 2)
9 : Swing PWM3 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
F : User Defined (C6-03 to C6-05)
Note:
• The carrier frequency for Swing PWM 1 to 4 is equivalent to 2.0 kHz. Swing PWM
applies a special PWM pattern to decrease the audible noise.
• Setting B uses a PWM pattern that decreases the leakage current that the drive detects
over long wiring distances. This can help decrease alarm detection and decrease
problems with the current monitor from leakage current over long wiring distances.
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection
= User Defined (C6-03 to C6-05)] to set this parameter.
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection
= User Defined (C6-03 to C6-05)] to set this parameter.
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency
Selection = User Defined (C6-03 to C6-05)] to set this parameter.
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
1.00
230
(0.00 - 2.50)
200 ms
230
(0 - 60000 ms)
Default
Ref.
(Range)
Determined by o2-04
231
(1 - F)
Determined by C6-02
232
(1.0 - 12.5 kHz)
Determined by C6-02
232
(1.0 - 12.5 kHz)
Determined by C6-02
232
(0 - 99)