YASKAWA HV600 Technical Reference page 749

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Register No.
(Hex.)
When you write parameter data to the EEPROM, you will enable the data on the RAM at the same time.
0900
This process saves the parameter changes even if you de-energize the drive.
This updates the data on the RAM, but does not write data to the EEPROM.
0910
If you de-energize the drive, you will lose the parameter changes.
Note:
• You can write the EEPROM to the drive a maximum of 100,000 times. Do not frequently execute the Enter command (0900 (Hex.)) that is
written to EEPROM.
• The Enter command register is write-only. If this register is read, it will cause a Register Number Error (02 (Hex.)).
• When the command data or broadcast message is transmitted to the drive, the Enter command is not necessary.
Automatic Enter Command
The drive can be set up to automatically perform an Enter command after a parameter is written. Parameter H5-11
enables and disables this feature.
Self-Diagnostics
The bypass can use Self-Diagnostics to verify the hardware transceiver on the control circuit. Self-Diagnostics
connects the transmission terminal to the reception terminal on the control circuit and transmits the data to itself to
makes sure that the bypass can communicate correctly.
Use this procedure to do Self-Diagnostics:
DANGER! Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized bypass. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the bypass is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below
50 Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the bypass is
safe. If you do work on the bypass when it is energized, it will cause serious injury or death from electrical shock.
1.
Energize the bypass.
2.
Set Z2-06 = 45 [Digital Input 6 Function (TB2-6) - Serial Hardware Test (RS-485)].
3.
De-energize the bypass.
4.
Connect a jumper between control circuit terminals TB2-6 and TB2-9 or TB2-10.
5.
Energize the bypass.
6.
When normal, the keypad will show PASS [Serial Communication Test].
Note:
If there is an error, the keypad will show CE [Serial Communication Error]. Disconnect the bypass from the network and test the
bypass again. If the error stays, there is a possible hardware problem. If there is no error, there is a possible network wiring
problem.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 10.29 Types of Enter Commands
Description
Figure 10.24 Self-Diagnostics Jumper Terminals
10.6 MEMOBUS/Modbus Communications
10
749