6.7 Parameter Setting Errors
Code
Name
Code
Name
oPE05
Run Cmd/Freq Ref Source Sel Err
Code
Name
oPE07
Analog Input Selection Error
Code
Name
oPE08
Parameter Selection Error
Code
Name
oPE09
PID Control Selection Fault
Note:
The drive detects this error if the PID control function selection is incorrect.
(When b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim])
510
Causes
These parameters are set at the same time:
• H1-xx = 62 [Speed Search from Fref]
• H5-22 = 1 [Speed Search from MODBUS =
Enabled]
Parameter S3-01 ≠ 0 [PI2 Control Enable Selection ≠
Disabled] and MFDI set for H1-xx = AD [Select PI2
Control PI Parameters] is ON or MFDI set for H1-xx
= 1AD [!Select PI2 Control PI Parameters] is OFF.
Causes
There is an option card installed on the drive.
The setting to assign the Run command or frequency
reference to an option card is incorrect.
Z1-39 = 3 [Drive/Bypass Source Select = Option
PCB] is set, but there is no option card connected.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB] is set, but there is no option card
connected.
b1-02 = 3 [Run Command Selection 1 = Option
PCB] is set, but there is no option card connected.
When S5-04 = 0 [HAND-OFF-AUTO Behavior =
Legacy], you set b1-02 ≠ 7, 8, or 9 [Run Command
Selection 1 ≠ AUTO Command + Term Run, AUTO
Command + Serial Run, or AUTO Command +
Option Run].
When S5-10 = 2 [AUTO Key Memory at Power
Down = AUTO Mode], you set b1-02 = 0 [Keypad].
Causes
The settings for H3-02 and H3-10 [MFAI Function
Selection] and H7-30 [Virtual Analog Input
Selection] overlap.
Causes
You set these parameters:
• S1-01 = 1 [Dynamic Noise Control = Enabled]
• Y4-42 ≠ 0 [Output Disconnect Detection Sel ≠
Disabled]
You set L6-02 [Torque Detection Level 1] < L6-14
[Motor Underload Level @ Min Freq].
Causes
These parameters are set at the same time:
• b5-01 = 1
• b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
And one of these parameters is set:
• d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠
0.0%]
• Y1-06 ≠ 0.0 [Minimum Speed ≠ 0.0%]
• Y4-12 ≠ 0.0 [Thrust Frequency ≠ 0.0%]
• YF-01≠ 0 [PI Aux Control Selection ≠ Disabled]
Parameter b5-01 = 3 and one of these parameters is
set at the same time:
• d2-02 ≠ 0.0
• Y1-06 ≠ 0.0
• Y4-12 ≠ 0.0
• YF-01≠ 0
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Possible Solutions
Remove one of the function settings.
• Set S3-01 = 0 to use H1-xx = AD or 1AD for the adjustments of
S3-06 [PI2 Control Proportional Gain] and S3-07 [PI2 Control
Integral Time] instead of the primary PI controller Proportional
and Integral adjustments.
• When PI2 Control is necessary, remove the MFDI function
setting.
Possible Solutions
Remove the option card from the drive. If it is compatible, install
the option card on the bypass control board.
Correct the parameter settings.
Connect an option card.
Set b1-02 = 7, 8, or 9.
Change the b1-02 or S5-10 setting.
Possible Solutions
Set H3-02, H3-10, and H7-30 correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
• Setting value 0 [Frequency Reference]
• Setting values F and 1F [Not Used]
Possible Solutions
Set S1-01 = 0 or Y4-42 = 0.
Set parameters to be L6-02 ≥ L6-14.
Possible Solutions
Correct the parameter settings.
Correct the parameter settings.