YASKAWA HV600 Technical Reference page 403

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

bit 10 : VLTS - Thermostat Fault
bit 11 to 15 : Reserved
Note:
The drive sets the bits in Hex.
S6-16: EMOVR Customer Safety Mode
No.
Name
(Hex.)
S6-16
EMOVR Customer Safety
Mode
(3247)
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
S6-17: EMOVR BAS Interlock Mode
No.
Name
(Hex.)
S6-17
EMOVR BAS Interlock
Mode
(3248)
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
S6-20: EMOVR Bypass Fault ON
No.
Name
(Hex.)
S6-20
EMOVR Bypass Fault ON
(324B)
Expert
0 : FB02
Wait For Interlock Timeout
1 : FB03
External Fault Bypass (EFB)
2 : FB05
Motor Overload
3 : FB06
External Overload 1
4 : FB07
External Overload 2
5 : FB08
Brownout Detected
6 : FB09
Blackout Detected
7 : FB10
Loss of Drive Communications
8 : FB13
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the status for the customer safety input (when programmed) that must occur for Emergency
Override to function.
Sets the status for the BAS Interlock input (when programmed) that must occur for Emergency
Override to function.
Enables bypass-specific faults.
5.11 S: Special Applications
Description
Description
Description
Default
(Range)
0
(0 - 2)
Default
(Range)
0
(0 - 2)
Default
(Range)
0
(0 - FFFF)
5
403