B: Application - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.5 b: Application

9.5

b: Application

b1: Operation Mode Selection
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection
1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
b1-08
Run Command Select in
PRG Mode
(0187)
b1-11
Run Delay @ Stop
(01DF)
b1-12
Run Delay Memory
Selection
(01E0)
b1-17
Run Command at Power
Up
(01C6)
b1-40
Deceleration Abort Time
(3BCF)
598
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Serial Communications
3 : Option PCB
7 : AUTO Command + Term Run
8 : AUTO Command + Serial Run
9 : AUTO Command + Option Run
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
Sets the reverse operation function. Disable reverse operation in fan or pump applications
where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
Sets the conditions for the drive to accept a Run command entered from an external source
when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
Sets the amount of time that the drive will not accept the Run command again after the
Run command is lost.
Note:
• This parameter will operate for both AUTO Mode and HAND Mode.
• This parameter will operate when the drive goes to sleep then wakes up.
• The time set in this parameter does not apply for faults or Auto-Restarts.
• When there is an active Run command while the time set in b1-11 is active, the
keypad will show a [Start Delay] message as specified by the o1-82 [Message Screen
Display] display format.
Sets how the drive saves the Run Delay Timer to the EEPROM during power loss.
0 : Disabled
1 : Only at Stop
2 : Running & Stop
Sets drive response when you apply power to drive that has an external Run command. Set
this parameter in applications where energizing or de-energizing the drive enables the Run
command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
Sets the maximum time until the drive shuts off the output to decelerate to stop.
Note:
Set this parameter to 0.0 s to disable this function.
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
1
187
(0 - 3)
7
188
(0 - 9)
1
189
(0 - 3)
1
191
(0, 1)
0
192
(0 - 2)
0.0 s
192
(0.0 - 6000.0 s)
2
193
(0 - 2)
1
195
(0, 1)
0.0 s
195
(0.0 - 6000.0 s)