YASKAWA HV600 Technical Reference page 195

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

b1-11: Run Delay @ Stop
b1-17: Run Command at Power Up
No.
Name
(Hex.)
b1-17
Run Command at Power Up
(01C6)
0 : Disregard Existing RUN Command
The drive does not start to operate the application when you apply power, even when there is an existing Run
command.
Enter the Run command again to operate the application.
Note:
When you energize the drive, if there is an existing Run command enabled from an external source,
1 : Accept Existing RUN Command
When there is an existing Run command, the drive starts to operate the application when you apply power.
b1-40: Deceleration Abort Time
No.
Name
(Hex.)
b1-40
Deceleration Abort Time
(3BCF)
Note:
Set this parameter to 0.0 s to disable this function.
When b1-40 > 0.0 s, the drive will coast-to-stop when you remove the Run command and decelerate for the time set
in b1-40. Refer to
Figure 5.14
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.13 Run Delay Memory Running & Stop
Sets drive response when you apply power to drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
Sets the maximum time until the drive shuts off the output to decelerate to stop.
for the timing chart.
Description
Description
5.2 b: Application
Default
(Range)
1
(0, 1)
on the keypad will flash quickly.
Default
(Range)
0.0 s
(0.0 - 6000.0 s)
195