YASKAWA HV600 Technical Reference page 630

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.10 H: Terminal Functions
H5: Serial Communication
No.
Name
(Hex.)
H5-01
Drive Node Address
(0425)
H5-02
Communication Speed
Selection
(0426)
H5-03
Communication Parity
Selection
(0427)
H5-04
Communication Error
Stop Method
(0428)
H5-05
Comm Fault Detection
Selection
(0429)
H5-06
Drive Transmit Wait
Time
(042A)
H5-08
Communication Protocol
Selection
(062D)
H5-09
CE Detection Time
(0435)
H5-10
Modbus Register 0025H
Unit Sel
(0436)
H5-11
Comm ENTER
Command Mode
(043C)
H5-14
BACnet Device Obj ID
LOW BITS
(310D)
H5-15
BACnet Device Obj ID
HIGH BITS
(310E)
H5-18
Motor Speed Filter over
Comms
(11A2)
630
Sets the communication slave address for drives.
Note:
• Restart the drive after you change the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
Sets the motor Stopping Method when the drive detects a Modbus Communication Error
condition.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Run at H5-34 (CE Go-To-Freq)
Sets the function that detects CE [Modbus Communication Error] issues during
MEMOBUS/Modbus communications.
0 : Disabled
1 : Enabled
Sets the time to wait to send a response message after the drive receives a command
message from the master.
Note:
Restart the drive after changing the parameter setting.
Selects the communication protocol.
0 : Modbus/MEMOBUS
1 : Metasys/N2
2 : Apogee/P1
3 : BACnet
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor
register 0025H (output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number.
Sets the upper bits of the BACnet device object ID as a 4-digit hexadecimal number.
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
1FH
306
(Determined by protocol)
3
306
(Determined by protocol)
0
307
(0 - 2)
3
307
(0 - 4)
1
308
(0, 1)
5 ms
308
(0 - 65 ms)
3
309
(0 - 3)
2.0 s
309
(0.0 - 10.0 s)
0
309
(0, 1)
0
309
(0, 1)
0001
309
(0000 - FFFF)
0000
310
(0000 - 003F)
0 ms
310
(0 - 100 ms)