Motor Wiring
Standard Motor Terminal
Block TB1
Model
H6BP
Tightening
AWG,
Torque
kcmil
(in lb)
B001
14-2
32
B002
14-2
32
B003
14-2
32
B004
14-2
32
B007
14-2
32
B011
14-2
32
B014
14-2
32
B021
14-2
32
B027
14-2
32
B034
14-2
32
B040
14-2
32
B052
14-2
32
B065
14-2
32
B077
6-2/0
120
*1
24-16 is acceptable for solid wire or ferrule use only.
208 V Enclosed Wire Gauges and Torques
Model
H6BP
Current Rating
Amps
D002
20
D003
20
D004
20
D007
20
D010
20
D016
20
D024
45
D030
63
D046
100
D059
100
D074
115
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 3.4 Output and Control Wiring
Ground Wiring
Tightening
Torque
AWG, kcmil
(in lb)
AWG, kcmil
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2
14-10, 8, 6-4, or
35, 40, 45, or 50
2-1/0
14-10, 8, 6-4, or
35, 40, 45, or 50
2-1/0
14-10, 8, 6-4, or
35, 40, 45, or 50
2-1/0
14-10, 8, 6-4, or
35, 40, 45, or 50
2-1/0
14-10, 8, 6-4, or
35, 40, 45, or 50
2-1/0
Table 3.5 Input Wiring
Standard Non-Fused
Input Disconnect Switch S1
Tightening Torque
AWG, kcmil
14-8
14-8
14-8
14-8
14-8
14-8
10, 8, or (6-2)
35, 40, or 50
10, 8, or (6-2)
35, 40, or 50
8-2/0
8-2/0
8-2/0
Control Wiring
A1
Terminal Blocks
Terminal Block
TB1, TB3-TB6
Tightening
Torque
AWG, kcmil
(in lb)
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
*1
24-16
4.4 to 5.3
24-18
Current Rating
(in lb)
Amps
19
15
19
15
19
15
19
20
19
25
19
40
60
70
200
110
200
125
200
150
3.3 Main Circuit Wiring
A1
A2
Terminal Blocks
TB2 (FE)
TB1-TB4 and TB6
Tightening
Torque
AWG, kcmil
(in lb)
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
8.85 to 10.62
26-14
With Option PM
Circuit Breaker CB1
Tightening Torque
AWG, kcmil
(in lb)
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
14-10 or 8-3/0
50 or 120
Tightening
Torque
(in lb)
4
4
4
4
4
4
4
4
4
4
4
4
4
4
3
83

Advertisement