Y2-01: Sleep Level Type
No.
Name
(Hex.)
Y2-01
Sleep Level Type
(3C64)
0 : Output Frequency
1 : Output Current
2 : Feedback
3 : Output Speed (RPM)
5 : Output Frequency (non-PID)
Note:
• Feedback depends on PID direction operation.
• When the Sleep Function is active, the keypad will show the "Sleep" Alarm.
Y2-02: Sleep Level
No.
Name
(Hex.)
Y2-02
Sleep Level
(3C65)
RUN
When the monitor data of the level type set in Y2-01 is less than this level for longer than the time set in Y2-03, the
drive will enter Sleep Mode.
Note:
• When you set this parameter to 0.0, this function will not be active.
• This function is active only when the drive operates in AUTO Mode.
• When Y2-01 = 5 [Output Frequency (non-PID)], the drive will disable the Sleep function when you set this parameter to 0.0.
• When Y2-01 ≠ 5, the drive will set the sleep level to the largest value from d2-02 [Frequency Reference Lower Limit], Y1-06 [Minimum
Speed], and Y4-12 [Thrust Frequency] when you set this parameter to 0.0.
Y2-03: Sleep Delay Time
No.
Name
(Hex.)
Y2-03
Sleep Delay Time
(3C66)
RUN
Y2-04: Sleep Activation Level
No.
Name
(Hex.)
Y2-04
Sleep Activation Level
(3C67)
RUN
Note:
When you set this parameter to 0.0, this function will not be active, and the Sleep Function will activate above the minimum speed (largest
value from d2-02 [Frequency Reference Lower Limit], Y1-06 [Minimum Speed], and Y4-12 [Thrust Frequency]).
Y2-05: Sleep Boost Level
No.
Name
(Hex.)
Y2-05
Sleep Boost Level
(3C68)
RUN
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the data source that the drive uses to know when to activate the Sleep Function.
Sets the level that the level type set in Y2-01 [Sleep Level Type] must be at for the time set in Y2-03
[Sleep Delay Time] for the drive to enter Sleep Mode.
Sets the delay time before the drive enters Sleep Mode when the drive is at the sleep level set in Y2-
02 [Sleep Level].
Sets the level above which the output frequency must increase to activate the Sleep Function when
Y2-01 = 0, 3, or 5 [Sleep Level Type = Output Frequency, Output Speed (RPM), or Output
Frequency (non-PID)].
Sets the quantity of boost that the drive applies to the setpoint before it goes to sleep.
5.13 Y: Application Features
Description
Description
Description
Description
Description
Default
(Range)
5
(0 - 5)
Default
(Range)
0.0
(0.0 - 6000.0)
Default
(Range)
5 s
(0 - 3600 s)
5
Default
(Range)
0.0
(0.0 - 6000.0)
Default
(Range)
0.00%
(0.00 - 600.00%)