YASKAWA HV600 Technical Reference page 620

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.10 H: Terminal Functions
No.
Name
(Hex.)
H2-62
Terminal M1-M2 Delay
Time
(1B48)
Expert
H2-63
Term M3-M4 Secondary
Function
(1B49)
Expert
H2-64
Terminal M3-M4 Logical
Operation
(1B4A)
Expert
H2-65
Terminal M3-M4 Delay
Time
(1B4B)
Expert
H2-66
Term M5-M6 Secondary
Function
(1B4C)
Expert
H2-67
Terminal M5-M6 Logical
Operation
(1B4D)
Expert
H2-68
Terminal M5-M6 Delay
Time
(1B4E)
Expert
H2-xx: MFDO Setting Values
Setting Value
Function
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
620
Sets the minimum on time used to output the logical calculation results from terminal M1-
M2.
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the
terminals assigned to functions by H2-02 [Term M3-M4 Function Selection].
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection]
and H2-63 [Term M3-M4 Secondary Function].
Sets the minimum on time used to output the logical calculation results from terminal M3-
M4.
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the
terminals assigned to functions by H2-03 [Terminal M5-M6 Function Select].
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection]
and H2-66 [Term M5-M6 Secondary Function].
Sets the minimum on time used to output the logical calculation results from terminal M5-
M6.
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency].
ON : Output frequency < E1-09.
OFF : Output frequency ≥ E1-09.
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is running.
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency reference ± L4-02.
The terminal deactivates when the output frequency > "L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree
Detection Width]". After the terminal deactivates, the terminal stays deactivated until the output frequency is at the
value of L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency < L4-01, or the output frequency ≤ "L4-01 + L4-02"
OFF : The output frequency > "L4-01 + L4-02"
The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal activates,
the terminal stays activated until the output frequency is at the value of "L4-01 - L4-02 [Speed Agree Detection
Width]".
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency > L4-01
OFF : The output frequency < "L4-01 - L4-02", or the output frequency ≤ L4-01
The terminal activates when the drive is ready and running.
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
0.1 s
279
(0.0 - 25.0 s)
F
279
(0 - FF)
0
279
(0 - 8)
0.1 s
279
(0.0 - 25.0 s)
F
279
(0 - FF)
0
279
(0 - 8)
0.1 s
279
(0.0 - 25.0 s)
Ref.
280
280
280
281
281
282
282

Advertisement

Table of Contents
loading

Table of Contents