YASKAWA HV600 Technical Reference page 288

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.7 H: Terminal Functions
OFF : Safety circuit fault or RUN/READY
Terminal H1-HC or terminal H2-HC is OFF (Open) (safety circuit fault), or the two terminals are ON or have short
circuited (RUN/READY).
2F: Maintenance Notification
Setting Value
Function
2F
Maintenance Notification
Tells the user about the maintenance period for these items:
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
Note:
Refer to "Alarm Outputs for Maintenance Monitors" for more information.
37: During Frequency Output
Setting Value
Function
37
During Frequency Output
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
Note:
The terminal deactivates in these conditions:
• During Stop
• During baseblock
• During DC Injection Braking (initial excitation)
38: Drive Enabled
Setting Value
Function
38
Drive Enabled
39: Watt Hour Pulse Output
Setting Value
Function
39
Watt Hour Pulse Output
Note:
Refer to "H2-06: Watt Hour Output Unit Selection" for more information.
288
The terminal activates when drive components are at their estimated maintenance period.
The terminal activates when the drive outputs frequency.
Figure 5.57 Active Frequency Output Time Chart
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
Outputs the pulse that shows the watt hours.
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference