YASKAWA HV600 Technical Reference page 281

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

L4-02: Speed Agree Detection Width
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ±
L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency
reference ± L4-02.
L4-01: Speed Agree Detection Level
4: Frequency Detection 1
Setting Value
Function
4
Frequency Detection 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.48 Speed Agree 1 Time Chart
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Figure 5.49 User-Defined Speed Agree 1 Time Chart
The terminal deactivates when the output frequency > "L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection
Width]". After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of L4-01.
Description
L4-02: Speed Agree Detection Width
Description
5.7 H: Terminal Functions
281
5