Yc: Foldback Features; Yf: Pi Auxiliary Control - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

YA-03: Setpoint 3
No.
Name
(Hex.)
YA-03
Setpoint 3
(3E5A)
RUN
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-39 [PID User Unit Display Digits] set the
unit, range, and resolution.
YA-04: Setpoint 4
No.
Name
(Hex.)
YA-04
Setpoint 4
(3E5B)
RUN
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-39 [PID User Unit Display Digits] set the
unit, range, and resolution.

YC: Foldback Features

YC parameters set Output Current Limit function.
Output Current Limit
The Output Current Limit function sets the current limit of motor. This function prevents long-term overload
conditions of motor when there is bearing degradation.
The drive will try to decrease the frequency reference to limit the output current. Parameter YC-02 [Current Limit]
sets the current limit setpoint. When the motor current increases to more than the setpoint, the drive will decrease the
output frequency.
YC-01: Output Current Limit Select
No.
Name
(Hex.)
YC-01
Output Current Limit Select
(3EBC)
0 : Disabled
1 : Enabled
YC-02: Current Limit
No.
Name
(Hex.)
YC-02
Current Limit
(3EBD)
RUN
Note:
Value is internally limited to 300% of the drive rated current set in n9-01 [Inverter Rated Current].

YF: PI Auxiliary Control

PI Auxiliary Control lets the drive control pressure when the PI Auxiliary Level is adequate. When the PI Auxiliary
Control Level decreases to the PI Auxiliary Control Setpoint set in parameter YF-03 [PI Aux Control Setpoint], the
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Sets the function to enable or disable the output current regulator.
Sets the current limit.
5.13 Y: Application Features
Description
Description
Description
Description
Default
(Range)
0.00
(0.00 - 600.00)
Default
(Range)
0.00
(0.00 - 600.00)
Default
(Range)
0
(0, 1)
5
Default
(Range)
0.0 A
(0.0 - 1000.0 A)
421

Advertisement

Table of Contents
loading

Table of Contents