YASKAWA HV600 Technical Reference page 751

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Register No.
(Hex.)
MFDO setting
bit 0
bit 1
bit 2
0009
bit 3 - 5
bit 6
bit 7
bit 8 - F
000A - 000C
Reserved
PI2 Control Setpoint
000D
000E
Reserved
Command selection setting
bit 0
bit 1
bit 2
bit 3
bit 4
000F
bit 5
bit 6 - B
bit C
bit D
bit E
bit F
0010 - 001F
Reserved
15FF
PID Feedback over comms
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
3004
Sets the hour and the minute in HHMM format.
• HH: 00 to 23 (decimal)
• MM: 00 to 59 (decimal)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Drive MFDO (terminal M1-M2)
1: ON, 0: OFF
Drive MFDO (terminal M3-M4)
1: ON, 0: OFF
Drive MFDO (terminal M5-M6)
1: ON, 0: OFF
Region Code
1: bit 7 function is enabled
Fault relay output (terminal MA/MB-MC)
1: ON, 0: OFF
Region Code
Units: 0.01%
Setting range: -100.00% to +100.00%
To enable this function, set MEMOBUS register 000F, bit 4 = 1.
Reserved
PID control target input
1: Enables target values from MEMOBUS/Modbus
Torque reference/torque limit input
1: Enables setting values from MEMOBUS/Modbus
Torque compensation input
1: Enables setting values from MEMOBUS/Modbus
PI2 control target input
1: Enables setting values from MEMOBUS/Modbus
PID feedback from the MEMOBUS/Modbus
1: Enables PID feedback (15FF (Hex.)) from MEMOBUS/Modbus
Reserved
Terminal S5 input for broadcast message
1: Enabled, 0: Disabled
Terminal S6 input for broadcast message
1: Enabled, 0: Disabled
Terminal S7 input for broadcast message
1: Enabled, 0: Disabled
Reserved
10.6 MEMOBUS/Modbus Communications
Description
10
751