5.11 S: Special Applications
S3-06: PI2 Control Proportional Gain
No.
Name
(Hex.)
S3-06
PI2 Control Proportional
Gain
(321F)
RUN
S3-07: PI2 Control Integral Time
No.
Name
(Hex.)
S3-07
PI2 Control Integral Time
(3220)
RUN
S3-08: PI2 Control Integral Max Limit
No.
Name
(Hex.)
S3-08
PI2 Control Integral Max
Limit
(3221)
RUN
S3-09: PI2 Control Output Upper Limit
No.
Name
(Hex.)
S3-09
PI2 Control Output Upper
Limit
(3222)
RUN
S3-10: PI2 Control Output Lower Limit
No.
Name
(Hex.)
S3-10
PI2 Control Output Lower
Limit
(3223)
RUN
S3-11: PI2 Control Output Level Sel
No.
Name
(Hex.)
S3-11
PI2 Control Output Level
Sel
(3224)
0 : Direct Acting (Normal Output)
When the feedback is higher than the setpoint, the speed decreases.
1 : Inverse Acting (Reverse Output)
When the feedback is lower than the setpoint, the speed decreases.
S3-12: PI2 Control Disable Mode Sel
No.
Name
(Hex.)
S3-12
PI2 Control Disable Mode
Sel
(3225)
RUN
0 : No Output (0%)
388
Sets the proportional gain of the PI2 Control. Set this parameter to 0.00 to disable proportional
control.
Sets the integral time for the suction pressure control. Set this parameter to 0.00 to disable the
integrator.
Sets the maximum output possible from the integrator.
Sets the maximum output possible from the PI Auxiliary Control function.
Sets the minimum output possible from the PI Auxiliary Control function.
Sets the PI2 controller output direction.
Sets what U5-20 [PI2 Control Output] will output when disabled.
Description
Description
Description
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
1.00
(0.00 - 25.00)
Default
(Range)
1.0 s
(0.0 - 360.0 s)
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
0.0%
(-100.0 - +100.0%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 2)