YASKAWA HV600 Technical Reference page 86

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

3.3 Main Circuit Wiring
Motor Wiring
Standard Motor
Terminal Block TB1
Model
H6BP
Tightening
AWG,
Torque
kcmil
(in lb)
A068
14-2
32
A080
14-8 or 6-2/
50 or 120
0
A104
14-8 or 6-2/
50 or 120
0
A130
(1-2) x (6)
(1-2) x 80
or (4) or (3-
or 100 or
4/0)
150
A154
6 - 350
275
kcmil
A192
6-350 kcmil
275
A248
(1-2) x (4-
(1-2) x 500
500 kcmil)
*1
24-16 is acceptable for solid wire or ferrule use only.
480 V Enclosed Wire Gauges and Torques
Model
H6BP
Current Rating
Amps
B001
20
B002
20
B003
20
B004
20
B007
20
B011
20
B014
20
B021
45
B027
45
B034
63
B040
63
B052
100
B065
100
B077
150
B096
150
B124
175
B156
250
B180
250
B240
400
B302
600
86
Ground Wiring
Terminal Blocks
Tightening
TB1, TB3-TB6
AWG,
Torque
kcmil
(in lb)
AWG,
kcmil
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14 - 2/0
120
24-16
14 - 2/0
120
24-16
Table 3.9 Input Wiring
Standard Non-Fused
Input Disconnect Switch S1
AWG, kcmil
14-8
14-8
14-8
14-8
14-8
14-8
14-8
10, 8 or (6-2)
10, 8 or (6-2)
10, 8 or (6-2)
10, 8 or (6-2)
8-2/0
8-2/0
8-3/0
14-10 or 8-3/0
4 - 4/0
3/0-350 kcmil
3/0-350 kcmil
(1-2) x (2/0-500 kcmil)
(1-2) x (2/0-500 kcmil)
A1
A1
Terminal Block
TB2 (FE)
Tightening
Tightening
AWG,
Torque
Torque
kcmil
(in lb)
(in lb)
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
Tightening Torque
Current Rating
(in lb)
Amps
20
15
20
15
20
15
20
15
20
20
20
25
20
35
35, 40, or 50
50
35, 40, or 50
60
35, 40, or 50
70
35, 40, or 50
80
200
110
200
115
120
150
50 or 120
150
225
250
225
250
225
250
(1-2) x 442
500
(1-2) x 442
600
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Control Wiring
A2
Terminal Blocks
TB1-TB4 and TB6
Tightening
AWG,
Torque
kcmil
(in lb)
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
With Option PM
Circuit Breaker CB1
AWG, kcmil
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
(14-10) or (8-3/0)
4-4/0
3/0-350 kcmil
3/0-350 kcmil
(1-2) x (2/0-500 kcmil)
(1-2) x (2/0-500 kcmil)
Panel
Terminal Block
TB4
Tightening
AWG,
Torque
kcmil
(in lb)
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
Tightening Torque
(in lb)
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
50 or 120
225
225
225
(1-2) x 442
(1-2) x 442