9.11 L: Protection Functions
No.
Name
(Hex.)
L5-08
Fault Reset Enable Select
Grp2
(0B2B)
L5-40
Low Feedback Flt Retry
Selection
(3670)
L5-41
Hi Feedback Flt Retry
Selection
(3671)
L5-42
Feedback Loss Fault
Retry Select
(3672)
L5-49
Fault Retry Speed Search
Select
(3679)
L5-50
Setpoint Not Met Fault
Retry Sel
(367A)
L5-51
Loss of Prime Fault Retry
Select
(367B)
L5-53
Thermostat Fault Retry
Selection
(3251)
636
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to
right, the digits set Uv1, ov, oH1, and GF, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
Sets the drive to do an Auto Restart when the drive detects an LFB [Low Feedback
Sensed] fault.
0 : No Retry
1 : Retry
Sets the drive to do an Auto Restart when the drive detects an HFB [High Feedback
Sensed] fault.
0 : No Retry
1 : Retry
Sets the drive to try an Auto Restart when it drive detects an FDBKL [WIRE Break] fault.
0 : No Retry
1 : Retry
Sets the drive to do a speed search at the start of a Fault Retry.
0 : Disabled
1 : Enabled
Sets the drive to try an Auto Restart when it detects an NMS [SetPoint Not Met] fault.
0 : No Retry
1 : Retry
Sets the drive to try an Auto Restart if it detects an LOP [Loss Of Prime] fault.
0 : No Retry
1 : Retry
Sets the drive to try an Auto Restart if it detects a VLTS [Thermostat Fault] fault.
Note:
• To use this function, set S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND
Analog Input]
• The drive will only restart after the Thermostat digital input de-activates and the L5-
04 [Interval Method Restart Time] timer is expired.
0 : No Retry
1 : Retry
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
1111
332
(0000 - 1111)
0
333
(0, 1)
0
334
(0, 1)
0
335
(0, 1)
1
335
(0, 1)
0
335
(0, 1)
0
335
(0, 1)
1
336
(0, 1)