YASKAWA HV600 Technical Reference page 680

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.18 U: Monitors
No.
Name
(Hex.)
U4-22
Modbus CmdData (hex)
(07DE)
U4-23
Option CmdData (hex)
(07DF)
U4-24
Number of Runs (Low)
(07E6)
U4-25
Number of Runs(High)
(07E7)
U4-61
Total EMOVR Run Time
(3096)
Expert
U5: PID Monitors
No.
Name
(Hex.)
U5-01
PID Feedback
(0057)
U5-02
PID Input
(0063)
680
Shows the operation signal (register 0001H) sent to the drive from MEMOBUS/Modbus
communications as a 4-digit hexadecimal number (zero suppress). The keypad shows the operation
signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
Shows the operation signal (register 0001H) sent to the drive from MEMOBUS/Modbus
communications as a 4-digit hexadecimal number. The keypad shows the operation signal as
specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
Shows the lower 4 digits of the drive run count.
Note:
The drive run count is an 8-digit number. Monitor U4-25 [Number of Runs(High)] shows the
upper 4 digits and U4-24 shows the lower 4 digits.
Shows the lower 4 digits of the drive run count.
Note:
The drive run count is an 8-digit number. Monitor U4-25 shows the upper 4 digits and U4-24
[Number of Runs (Low)] shows the lower 4 digits.
Shows the length of time that the drive operated in Emergency Override Mode.
Unit: 1 min
Note:
• The maximum value is 60,000 min.
• This monitor does not accumulate operation time when S6-07 = 1 [EMOVR Fault Suppression
Mode = Test Mode].
Shows the PID control feedback value.
Unit: 0.01%
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-
39 [PID User Unit Display Digits] set the unit, range, and resolution.
Shows the change between the PID setpoint and PID feedback (the quantity of PID input) as a
percentage of the maximum output frequency.
Unit: 0.01%
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
MFAO Signal Level
10 V = Maximum frequency
(-10 V to +10 V)
10 V: Maximum frequency
(0 V to +10 V)