Advertisement

10.4
APOGEE FLN (P1) Communications
This section gives detailed information about the parameters, error codes and communication procedures for
APOGEE FLN (P1) communications.
APOGEE FLN Set-Up
A Yaskawa America, Inc. representative is responsible for proper configuration of the drive for its primary
application, while a Siemens Building Technologies, Inc. representative is responsible for field panel programming to
make use of the drive functionality in the building automation system. As such, there must be coordination between
the Yaskawa America and Siemens Building Technologies representatives to ensure that the programming of the drive
is consistent with the particular application requirements. After verifying that the drive installation and wiring are
correct, apply power to the drive.
communication and control.
Parameter No.
Frequency Reference Selection 1
b1-01
Run Command Selection 1
b1-02
Drive Node Address
H5-01
H5-02
Communication Speed Selection
H5-08
Communication Protocol Selection
Z3-16
Apogee Run Enable LD035
NOTICE: Damage to Equipment. Do not change the APOGEE FLN (P1) communication parameter settings. A Yaskawa
representative must set the parameters to their correct values. Incorrect parameter settings can cause damage to the drive or
building equipment.
Communication Specifications
Table 10.8
lists the specifications for the APOGEE FLN (P1).
Item
Interface
Communication parameter
Communication protocol
Number of possible units to connect
Communication with the Controller
This section gives information about the settings for the termination resistor and how to connect to APOGEE FLN
(P1) communications.
Connect Communications Cable
Use this procedure to start communication between the controller and bypass.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 10.7
lists the parameters and values required for proper APOGEE FLN
Table 10.7 Drive APOGEE FLN Communication Parameter Settings
HOA Keypad Display
Table 10.8 APOGEE FLN (P1) Specifications
FLN
RS-485
Communication speed: 4.8 kbps, 9.6 kbps
Data length: 8 bit (fixed)
Parity: even, odd, none
Stop bit: 1 bit (fixed)
APOGEE FLN P1
Maximum: 97 units for each FLN network segment
10.4 APOGEE FLN (P1) Communications
APOGEE FLN Setting
2: Serial Communications
2: Serial Communications
or
8: AUTO Command + Serial Run
Select the drive address (default = 1Fh (31 dec))
2: 4800 bps or 3: 9600 bps
2: Apogee/P1
1: Enabled
Specification
10
717