9.18 U: Monitors
No.
Name
(Hex.)
Ub-15
Previous Fault MMDD
(878E)
Ub-16
Previous Fault HHMM
(878F)
Ub-17
Contactor Voltage
(8790)
Ub-18
Software Version
(8791)
Ub-19
Date Year YYYY
(8792)
Ub-20
Date Month Day MMDD
(8793)
Ub-21
Time Hour Min HHMM
(8794)
Ub-22
Bypass Analog Input
(8795)
Ub-23
Motor 1 Overload
(8796)
Ub-24
Motor 2 Overload
(8797)
Ub-94
Bypass CPU Usage
(87DD)
Ub-95
Line Frequency
(87DE)
Ub-96
Byp Phase Loss Level
(87DF)
Ub-99
Desired HV600 software
version
(87E2)
Expert
UC: BACnet Diagnostic Monitors
No.
Name
(Hex.)
UC-01
BN MSTP Net Health
(3DB0)
UC-02
BACnet Tokens Rx
(3DB1)
UC-03
BACnet Tokens Tx
(3DB2)
UC-04
BACnet Messages Rx
(3DB3)
UC-05
BACnet Messages Tx
(3DB4)
UC-06
MSTP Next Node Addr
(3DB5)
UC-07
MSTP Prev Node Addr
(3DB6)
UC-08
MSTP H MAC Found
(3DB7)
686
Displays the month and day of the previous fault.
Unit: -
Displays the hour and minute of the previous fault.
Unit: -
Displays the measured voltage for the power going to the contactor coils.
Unit: 1 Vac
Displays the software version currently programmed into the bypass.
Unit: -
Displays the current year.
Unit: -
Displays the current date (Month and Date).
Unit: -
Displays the current time (Hours and Minutes).
Unit: -
Bypass MFAI level
Unit: 0-100%
Motor 1 Overload level
Unit: 0-100%
Motor 2 Overload level
Unit: 0-100%
Current Bypass CPU Load
Unit: 0-100%
Calculated AC line frequency
Unit: Hz
Current Phase Loss level
Unit: 0-100%
Shows the latest version of HV600 software that this version of HV600 Bypass software supports.
Unit: -
Shows a number between 0.0% and 100.0% that identifies the health of the MSTP network. This
number is dependent on the number of CRC errors, token losses, token retries, and net deadtime
perceived.
Unit: 0.1%
Shows the number of received MSTP Tokens after you energize the drive.
Unit: 1
Shows the number of transmitted MSTP Tokens after you energize the drive.
Unit: 1
Shows the number of messages with data (non-token, non-polling) received by the drive.
Unit: 1
Shows the number of messages with data (non-token, non-polling) transmitted by the drive.
Unit: 1
Shows the next known node in the MSTP loop. This is the node to which the drive will pass the
token.
Unit: Hex
Shows the previous known node in the MSTP loop. This is the node from which the drive received
the token.
Unit: Hex
Shows the highest MAC address found on the network. This will report the highest value MAC
address to which the token was passed by any node on the MSTP loop.
Unit: Hex
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available