YASKAWA HV600 Technical Reference page 645

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
o3-04
Select Backup/Restore
Location
(0B3E)
o3-06
Auto Parameter Backup
Selection
(0BDE)
o3-07
Auto Parameter Backup
Interval
(0BDF)
o4: Maintenance Monitors
No.
Name
(Hex.)
o4-01
Elapsed Operating Time
Setting
(050B)
o4-02
Elapsed Operating Time
Selection
(050C)
o4-03
Fan Operation Time
Setting
(050E)
o4-05
Capacitor Maintenance
Setting
(051D)
o4-07
Softcharge Relay
Maintenance Set
(0523)
o4-09
IGBT Maintenance
Setting
(0525)
o4-11
Fault Trace/History Init
(U2/U3)
(0510)
o4-12
kWh Monitor
Initialization
(0512)
o4-13
RUN Command Counter
@ Initialize
(0528)
o4-22
Time Format
(154F)
RUN
o4-23
Date Format
(1550)
RUN
o4-24
bAT Detection Selection
(310F)
RUN
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the storage location for drive parameters when you back up and restore parameters.
This parameter is only available on an HOA keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
Sets the function that automatically backs up parameters. This parameter is only available
on an HOA keypad.
0 : Disabled
1 : Enabled
Sets the interval at which the automatic parameter backup function saves parameters from
the drive to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
Description
Sets the initial value of the cumulative drive operation time in 10-hour units.
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
Sets the value from which to start the cumulative drive cooling fan operation time in 10-
hour units.
Sets the U4-05 [CapacitorMaintenance] monitor value.
Sets the U4-06 [PreChargeRelayMainte] monitor value.
Sets the U4-07 [IGBT Maintenance] monitor value.
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].
0 : Disabled
1 : Enabled
Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5
Digits].
0 : No Reset
1 : Reset
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs
(Low)], and U4-25 [Number of Runs (High)].
0 : No Reset
1 : Reset
Sets the time display format. This parameter is only available on an HOA keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
Sets the date display format. This parameter is only available on an HOA keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
Sets operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM [Keypad
Time Not Set].
0 : Disable
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
9.13 o: Keypad-Related Settings
Default
(Range)
0
(0 - 3)
1
(0, 1)
1
(0 - 3)
Default
(Range)
0 h
(0 - 9999 h)
1
(0, 1)
0 h
(0 - 9999 h)
0%
(0 - 150%)
0%
(0 - 150%)
0%
(0 - 150%)
0
(0, 1)
0
(0, 1)
0
(0, 1)
1
(0 - 2)
2
(0 - 2)
0
(0 - 2)
Ref.
366
366
366
Ref.
367
367
367
367
367
368
368
368
368
368
369
9
369
645