YASKAWA HV600 Technical Reference page 309

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

H5-08: Communication Protocol Selection
No.
Name
(Hex.)
H5-08
Communication Protocol
Selection
(062D)
0 : Modbus/MEMOBUS
1 : Metasys/N2
2 : Apogee/P1
3 : BACnet
H5-09: CE Detection Time
No.
Name
(Hex.)
H5-09
CE Detection Time
(0435)
H5-10: Modbus Register 0025H Unit Sel
No.
Name
(Hex.)
H5-10
Modbus Register 0025H
Unit Sel
(0436)
0 : 0.1 V units
1 : 1 V units
H5-11: Comm ENTER Command Mode
No.
Name
(Hex.)
H5-11
Comm ENTER Command
Mode
(043C)
0 : ENTER Command Required
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the Enter
command.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
H5-14: BACnet Device Obj ID LOW BITS
No.
Name
(Hex.)
H5-14
BACnet Device Obj ID
LOW BITS
(310D)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.66 Drive Transmit Wait Time
Selects the communication protocol.
Sets the detection time for CE [Modbus Communication Error] issues when communication stops.
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H
(output voltage reference monitor).
Sets the function to make the Enter command necessary to change parameters through MEMOBUS/
Modbus communications.
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number.
Description
Description
Description
Description
Description
5.7 H: Terminal Functions
Default
(Range)
3
(0 - 3)
Default
(Range)
2.0 s
(0.0 - 10.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0001
(0000 - FFFF)