Use this derated torque pattern for torque loads proportional to two times the rotation speed. For example, fans and
pumps.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
8 : High Trq, 50Hz, 25% Vmin boost
Use this pattern when moderate torque is necessary during start up.
Select this pattern only in these conditions:
• The wiring distance between the drive and motor is 150 m (492.1 ft) minimum.
• There is an AC reactor connected to the drive output.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
9 : High Trq, 50Hz, 65% Vmin boost
Use this pattern when high torque is necessary during start up.
Select this pattern only in these conditions:
• The wiring distance between the drive and motor is 150 m (492.1 ft) minimum.
• There is an AC reactor connected to the drive output.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
A : High Trq, 60Hz, 25% Vmin boost
Use this pattern when moderate torque is necessary during start up.
Select this pattern only in these conditions:
• The wiring distance between the drive and motor is 150 m (492.1 ft) minimum.
• There is an AC reactor connected to the drive output.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
5.5 E: Motor Parameters
A192 - A248, B096 - B302
A192 - A248, B096 - B302
A192 - A248, B096 - B302
247